All Systems Operational

Updated a few seconds ago

Critical Power




Operational

Critical Cooling




Operational

Internet Transit




Operational

Dashboard




Operational

Access Control




Operational

Facility




Operational

Optical Transport Network




Operational

1

Upcoming Maintenances

3

Incidents Last 30 Days

10

Maintenances Last 30 Days

External Services

Locations

Scheduled Maintenance

Schedule

August 4, 2026 6:00AM - 6:00PM MST

Components

Critical Power, Critical Cooling, Facility

Locations

DCX-GYR1

Description

DCX Operations has opened a Planned Maintenance Window effective immediately. Power washing for equipment yard and equipment.

History (Last 7 days)

DCX OTN FlappingOperational

Incident Status

Operational


Components

Optical Transport Network


Locations

DCX-GYR1, DCX-PHX2




July 29, 2026 8:29AM MST
RESOLVED

The dark fiber provider has completed remediation. The south paths are now available as failover candidates fully restoring redundancy. Event is concluded.

July 27, 2026 8:26PM MST
IDENTIFIED

The dark fiber provider has indicated that construction that is occurring near a vault damaged a 144 count cable which the DCX south path fibers are a part of. They are in process of remediation. DCX OTN service will remain on redundant path during this time.

July 27, 2026 4:03PM MST
IDENTIFIED

The dark fiber provider is in process of remediating the impacted path. DCX OTN service will remain on redundant path during this time.

July 27, 2026 3:57PM MST
IDENTIFIED

The DCX OTN for path B (previously referred to as south path) was experiencing flapping due to an unknown event relating to the dark fiber. The event is causing significant increase in loss but not enough for protection to have automatically engaged. This resulted in unstable flapping service. DCX operations manually engaged protection to cut the circuit over to its redundant path to stabilize service. DCX operations has engaged the dark fiber provider to investigate/remediate the primary path.

Incident Status

Degraded Performance


Components

Critical Cooling


Locations

DCX-GYR1




July 24, 2026 7:32PM MST
RESOLVED

HVAC technician identified high head pressure causing compressor shut off. Root cause is the extreme temperatures pushing the units outside of their operating bounds resulting in the high head pressure/compressor shut off. Measures have been implemented to reduce the ambient temperature around the units to allow them to operate. Further longer term measures will be investigated and implemented by DCX. Systems are currently operational and environmental are nominal.

July 24, 2026 3:57PM MST
INVESTIGATING

At 2:34pm MST, alerts were received indicating that UPS2A temperatures were increasing. Upon investigation it was found that two of the three units were not functioning. Emergency measures were implemented to manage temperature while working to secure an HVAC technician to diagnose and remediate.

Description

DCX Operations has opened an Emergency Maintenance Window effective immediately. UPS2B HVAC1 and HVAC3 units are struggling to remain operational and provide cooling. An HVAC technician has been dispatched to diagnose and remedy.


Components

Critical Cooling


Locations

DCX-GYR1


Schedule

July 24, 2026 4:05PM - July 24, 2026 10:00PM MST



July 24, 2026 7:30PM MST
UPDATE

HVAC technician identified high head pressure causing compressor shut off. Root cause is the extreme temperatures pushing the units outside of their operating bounds resulting in the high head pressure/compressor shut off. Measures have been implemented to reduce the ambient temperature around the units to allow them to operate.

July 24, 2026 4:05PM MST
UPDATE

Scheduled maintenance is starting.